500 Series
A Block
AA Block
ACT-2V
ACT-SI
ACT-SV
AL Block
APT-35L
B Block
B S/H Block
BD100
BD120
BD130
BD140
BD200
BD300
BD320
BD901
BD902
BM100
BM120
BM130
BM140
BM191
BM191E
BM200
BM303
BM320
BM901
BM902
BM916
BM9431
BM9432
BU191
C-Block
C1-Block
C600
CSM-1
D-Block
DCC-8
DIN100
DIN120
DIN130
DIN140
DIN200
DIN300
DIN320
DIN350
DIN360
DIN370
DIN380
DIN400
DIN500
DIN700
DIN710
DIN720
E Block
EI400
E1-1C0 / E1-1C3
E1-FREQ
E1-VAR Series
E1-W Series
FTI-1
FTI-1D
G Block
H Block
I Block
IEC61508
J Block
K Block
KK Block
L Block
L900
L900RG Mark II
M Block
MDM-11
MicroDIN
MicroFREQ A-F
MicroFREQ F-A
MicroFREQ F-F
MicroMATH
MIN100
MIN120
MIN130
MIN140
MIN200
MIN300
MIN310
MIN320
MIN350
MIN360
MIN380
MIN400
MIN500
MIN710
MIN720
N Block
NAMUR NE43
P Block
PU700
QC Series
R Block
RTR-2
RTI-2
RTI-2D
RTM-8
RTP-2
RTT-2
RTT-3
S Block
SC200
SEL300
SI300-20
SI300 & SI310
SI320, SI330 & SI340
T Block
T100
T120
T130
TCI-2
TCI-2D
TCR-2
TCT-3
VVH-3
WVT-3
WWH-3

IEC61508 (SIL) RATED INSTRUMENTS: 

For full FMEDA reports please contact our Sales Office.

If the product you require is not available to buy online, please complete the Enquiry Form.

BM100 - Single Level Trip Amplifier

BM100
This replaces the MIN100.

Function: Single Level Trip Amplifier from a single process signal input. The trip action can be arranged so that the Alarm condition can be above (High Trip) or below (Low Trip) the set point, and that the relay can be either normally energised to de-energise in the Alarm condition (Fail-Safe), or normally de-energised to energise in the Alarm condition (Non Fail-Safe).

Power supply: DC powered

 
  Proof Test Interval
Application 1 year 6 months
4-20mA Input & High Alarm Trip SIL 2 SIL 2
4-20mA Input & Low Alarm Trip SIL 1 SIL 2
0-10vdc Input & High Alarm Trip SIL 2 SIL 2
0-10vdc Input & Low Alarm Trip SIL 1 SIL 2
Other Inputs (see data sheet) & High Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & Low Alarm Trip SIL 1 SIL 2

This summary applies to BM100's built in Fail Safe mode

BD100 - Single Level Trip Amplifier

BD100
This replaces the DIN100.

Function: Single Level Trip Amplifier from a single process signal input. The trip action can be arranged so that the Alarm condition can be above (High Trip) or below (Low Trip) the set point, and that the relay can be either normally energised to de-energise in the Alarm condition (Fail-Safe), or normally de-energised to energise in the Alarm condition (Non Fail-Safe).

Options include: Double Pole Change Over relays

Power supply: mains powered
  Proof Test Interval
Application 1 year 6 months
4-20mA Input & High Alarm Trip SIL 2 SIL 2
4-20mA Input & Low Alarm Trip SIL 2 SIL 2
0-10vdc Input & High Alarm Trip SIL 2 SIL 2
0-10vdc Input & Low Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & High Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & Low Alarm Trip SIL 1 SIL 2

This summary applies to BD100's built in Fail Safe mode

BM200 - Frequency to Current / Voltage Converter


This replaces the MIN200.

BM200Function: Conversion of an input frequency to a linearly proportional, isolated output current or voltage. The BM200 can be used to monitor the speed of rotating machinery and can be followed by a BM100/BM120 trip amplifier to give alarm, control or shutdown facilities at preset levels of speed. It is ideally suited for use with turbine flow meters to give an analogue measurement of flow rate, and with proximity detectors for non-contact speed measurement. The BM200 incorporates both a sensitivity adjustment and a reference voltage to allow a variety of sensor types to be used.

 

Power supply: DC powered
 

Proof Test Interval

Application 1 year PTI 6 months PTI 3 month PTI
Low output dangerous, out of range not detected SIL 1 SIL 1 SIL 1
Low output dangerous, out of range detected SIL 2 SIL 2 SIL 2
High output dangerous, out of range not detected SIL 2 SIL 2 SIL 2
High output dangerous, out of range detected SIL 2 SIL 2 SIL 3

 

BD200 - Frequency to Current / Voltage Converter


This replaces the DIN200.

BD200Function: Conversion of an input frequency to a linearly proportional, isolated output current or voltage. The BD200 can be used to monitor the speed of rotating machinery and can be followed by a BD100/BD120 trip amplifier to give alarm, control or shutdown facilities at preset levels of speed. It is ideally suited for use with turbine flow meters to give an analogue measurement of flow rate, and with proximity detectors for non-contact speed measurement. The BD200 incorporates both a sensitivity adjustment and a reference voltage to allow a variety of sensor types to be used.



Power supply: mains powered
 

Proof Test Interval

Application 1 year PTI 6 months PTI 3 month PTI
Low output dangerous, out of range not detected SIL 1 SIL 1 SIL 1
Low output dangerous, out of range detected SIL 2 SIL 2 SIL 2
High output dangerous, out of range not detected SIL 1 SIL 2 SIL 2
High output dangerous, out of range detected SIL 2 SIL 2 SIL 3

 

BU191 - Flow Meter Single Level Trip Amplifier

BU191
Function: The BU191 is a universally powered Alarm Unit suitable for use with a number of different VA Flowmeters. It can be configured for use as a Low or a High Flow Alarm, as required. Each different VA Flowmeter will require a different sensor head for mechanical reasons but in all cases the operation of the Alarm Unit is the same. The sensor heads supplied come with 1M of cable for connection to the Alarm Unit. The BU191 has an “Instrument Fault” indication LED (Amber) which is triggered following loss of power or loss of connection to the Head. This LED can only be cleared by restoring power or replacing the head, passing the float from the Alarm State to the Healthy State and pressing the RESET button to initiate the Stable condition. The BU191 incorporates a sensitivity adjustment to cater for different VA Flowmeters.

Power supply: universal
  Proof Test Interval
Application 1 year 1 month
With BHRAGK41, BH1100 and BH1300 Sensor Heads SIL 2 SIL 3

 

BM120 - Dual Level Trip Amplifier

BM120
This replaces the MIN120.

Function: Dual Level Trip Amplifier from a single process signal input. The trip action can be arranged so that the Alarm condition can be above (High Trip) or below (Low Trip) each of the set points, and that the relays can be either normally energised to de-energise in the Alarm condition (Fail-Safe), or normally de-energised to energise in the Alarm condition (Non Fail-Safe).

Power supply: DC powered

 
  Proof Test Interval
Application 1 year 6 months
4-20mA Input & High Alarm Trip SIL 2 SIL 2
4-20mA Input & Low Alarm Trip SIL 2 SIL 2
0-10vdc Input & High Alarm Trip SIL 2 SIL 2
0-10vdc Input & Low Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & High Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & Low Alarm Trip SIL 1 SIL 2

This summary applies to BM120's built in Fail Safe mode
Please note, that for High & Low Alarm trips, the above SIL for Low Alarm Trip should be used

BD120 - Dual Level Trip Amplifier

BD120
This replaces the DIN120.

Function: Dual Level Trip Amplifier from a single process signal input. The trip action can be arranged so that the Alarm conditions can be above (High Trip) or below (Low Trip) the set point, and that the relays can be either normally energised to de-energise in the Alarm condition (Fail-Safe), or normally de-energised to energise in the Alarm condition (Non Fail-Safe).

Power supply: mains powered

 
  Proof Test Interval
Application 1 year 6 months
4-20mA Input & High Alarm Trip SIL 2 SIL 2
4-20mA Input & Low Alarm Trip SIL 2 SIL 2
0-10vdc Input & High Alarm Trip SIL 2 SIL 2
0-10vdc Input & Low Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & High Alarm Trip SIL 2 SIL 2
Other Inputs (see data sheet) & Low Alarm Trip SIL 1 SIL 2

This summary applies to BD120's built in Fail Safe mode
Please note, that for High & Low Alarm trips, the above SIL for Low Alarm Trip should be used

BM303 - Isolating Signal Converter

BM303
This replaces the MIN300.

Function: Isolating signal converter which will convert a range of process signals into standard transmission voltage or current signals. The BM303 first conditions the signal before feeding it through an opto-isolating circuit. Both the input and the output stages of the instrument are powered from separate secondaries of the inverter maintaining 3 port isolation.

Options include: a Signal Inverter, a Passive Output (Current Sink), Subtractor and an Adder or Averager. In the last three cases the inputs are restricted to mA or Voltage and the BM303 can only accept two inputs.

Power supply: DC powered
  Proof Test Interval
Application 1 year 6 months
For all combinations of Inputs & Outputs SIL 2 SIL 2
 
BD300 - Isolating Signal Converter: mains powered

BD300
This replaces the DIN300.

Function: Isolating signal converter which will convert a range of process signals into standard transmission voltage or current signals. The BD300 first conditions the signal before feeding it through an opto-isolating circuit. Both the input and the output stages of the instrument are powered from separate secondaries of the mains transformer thus maintaining 3 port isolation.

Options include: a signal Inverter, a Passive Output (Current Sink), a Subtractor and an Adder or Averager. In the last three cases the inputs are restricted to mA or Voltage and the BD300 can only accept two inputs.

Power supply: mains powered
  Proof Test Interval
Application 1 year 6 months
For all combinations of Inputs & Outputs SIL 2 SIL 2
BM320 - Dual Output Isolating Signal Converter

BM320
This replaces the MIN320.

Function: Isolating signal converter which will convert a range of process signals into two independently isolated current or voltage outputs. The BM320 is ideally suited to providing signals for both local indication/control and remote monitoring and control from the one input signal. The BM320 still maintains three port isolation with the input and both output circuits powered from separate secondaries of the DC/DC converter.

Options include: AC Current input and AC Voltage input ranges. The instrument comes as standard with both Active and Passive outputs - simply wire into the required terminals.

Power supply: DC powered
  Proof Test Interval
Application 1 year 6 months
For all combinations of Inputs & Outputs SIL 2 SIL 2

 

BD320 - Dual Output Isolating Signal Converter: mains powered

BD320
This replaces the DIN320.

Function: Isolating signal converter which will convert a range of process signals into two independently isolated current or voltage outputs. The BD320 is ideally suited to providing signals for both local indication/control and remote monitoring and control from the one input signal. The BD320 still maintains three port isolation with the input and both output circuits powered from separate secondaries of the transformer.

Options include: AC Current input and AC Voltage input ranges. The instrument comes as standard with both Active and Passive outputs - simply wire into the required terminals.

Power supply: mains powered
  Proof Test Interval
Application 1 year 6 months
For all combinations of Inputs & Outputs SIL 2 SIL 2

 

BM916 - Low Input Impedance Isolating Signal Converter

BM916
This replaces the MIN300.

Function: Low input impedance (10 ohms) isolating signal converter for use in 4 to 20mA loops. The BM916 will convert the 4 to 20mA signal into standard active and passive (current sink) transmission voltage or current signals. The BM916 first conditions the signal before feeding it through an opto-isolating circuit. Both the input and the output stages of the instrument are powered from separate secondaries of the inverter maintaining 3 port isolation.

Options include: a Signal Inverter

Power supply:  DC powered
  Proof Test Interval
Application 1 year 6 months
For all combinations of Inputs & Outputs SIL 2 SIL 2

 


top back